Specifications
78 PRT-WX-DIN Using Protege WX Installation and Programming Manual | June 2013
Type
Service Type: The type of service that is programmed determines the operation that this service performs.
This also determines the programming screens that follow in each of the sub sections as the programming
of services can contain many features and options dependent on this selection. The following section
provides an explanation of each service type. Services require the use of onboard hardware devices or
expansion devices.
Contact ID: Sends alarms, tests and events using the Contact ID reporting format to a monitoring
station capable of receiving the Contact ID format. This service will share the modem with the SIA,
Monitor Phone and ModBUS remote services if they are running.
Report IP: Allows the Protege System controller to send alarm and activation information over an IP
connected network. The Report IP Service supports multiple formats and allows the connection to third
party reporting if required.
Service Mode: The service mode determines how this service operates with the system controller. By
default a service is set to start with the operating system. Setting a service to Start With The Operating
System (Start With O/S) allows the service to operate automatically, if the system controller is reset or
restarts the service will automatically restart with the operating system. To only start and stop the service
manually select the manual option.
Contact ID
The Contact ID Service is used to sends alarms, tests and events using the Contact ID reporting format to a
monitoring station capable of receiving the Contact ID format.
Contact ID | General
Client Code: The client code is used to identify the system to the remote monitoring company when a
report is generated. The client code will accept hexadecimal numbers however this will be dependent on
the ability of the receiver and should be verified before configuration.
PABX Number: The PABX phone number is dialed to gain an outside line if the system is connected to a
internal phone extension. The PABX phone number can also be programmed with a schedule in the case
that between certain times the phone line is directly connected with an outside line.
Phone Number 1: The primary phone number will be dialed by the contact ID service when it first is
initiated to report an event. The sequence of telephone number dialing is limited by the number of dialing
attempts and the method of dialing that is configured (alternate or sequential).
Phone Number 2: The secondary phone number will be dialed by the contact ID service if a connection
with the central station cannot be made on the primary phone number. This may be dialed after the total
number of attempts is reached on the primary or sequential until the total number of attempts is reached for
the primary and secondary numbers. The sequence of telephone number dialing is limited by the number of
dialing attempts and the method of dialing that is configured (alternate or sequential).
Phone Backup: The backup phone number will be dialed by the contact ID service if a connection with the
central station cannot be made on either the primary or secondary phone number. This will be dialed after
the total number of attempts is reached on the primary and secondary numbers. The backup number will
be dialed for the configured number of dialing attempts programmed for the service.