Specifications
PRT-WX-DIN Using Protege WX Installation and Programming Manual | June 2013
71
Address:
Module Type: The type of module that the output is attached to.
Module Address: The address of the module that the output is attached to.
Module Output: The index of the specified output on that module.
Configuration:
Activation Schedule: The activation schedule is programmed to activate the output at a certain time of the
day or to activate the output between certain hours. The schedule will be checked at the start and end
times and if the start is valid the output will be activated, if the end time of the schedule is valid the output
will be deactivated. If an output is controlled by an operator, user or other function during this activation time
and is deactivated it will remain in the deactivated state. Setting the recheck schedule option for the output
will force the output to have the schedule verified every 60 second period. This will prevent the output from
being controlled manually as the schedule will override the manual operation.
Always Verify Schedule: When enabled the output will re-verify the schedule that is programmed every 60
seconds. If the output is meant to be activated but is in a deactivated state the system will activate the
output.
Activation Time: Setting an activation time for an output will mean that any device controlling the output will
only activate the output for the programmed time.
Activation Retrigger: When enabled, if an output receives a command to activate for a defined period, and
during that time it receives a second command to activate, this option retriggers the output for the second
period. If this option is disabled, the second command is ignored.
Outputs | Options
General
Log Output Events: When enabled the output will generate an event whenever it is activate or deactivated.
The output will still perform all functions that are programmed if this is not enabled. When using output's as
automation control outputs it is recommended to disable the event logging option to reduce the impact on
the event log buffer.
Invert Output: When enabled the output will operate inverted. Deactivation will result in the output being
activated and activation will result in the output being deactivated.
Preset State
Preset Controller Power Up: When enabled, the state of the output will be set when the controller is reset
or powered up for the first time.
Output Turns On When Controller Powers Up: Defines the state of the state of the output when the
Preset Controller Power Up option is enabled. If enabled, the output will be activated. If disabled, the output