Specifications
PRT-WX-DIN Using Protege WX Installation and Programming Manual | June 2013
7
Technical Specifications
The following specifications are important and vital to the correct operation of the Controller. Failure to adhere to
the specifications will result in any warranty or guarantee that was provided becoming null and void. Integrated
Control Technology continually strives to increase the performance of its products. As a result these
specifications may change without notice. We recommend consulting the ICT website
(http://www.incontrol.co.nz) for the latest documentation and product information.
Operating Voltage 11-14V DC
Operating Current 120mA (Typical)
DC Output (Auxiliary) 0.7A (Typical) Electronic Shutdown at 1.1A
Bell DC Output (Continuous) 8 Ohm 30W Siren or 1.1A (Typical) Electronic Shutdown at 1.6A
Bell DC Output (Inrush) 1500mA
Total Combined Current* 3.4A (Max)
Electronic Disconnection 9.0VDC
Communication (Ethernet) 1 10/100Mbps Ethernet Communication Link
Communication (Serial) 1 RS-485 Communication Interface Port
Communication (Modem) 1 2400bps Modem Communication
Readers (Standard Mode) 2 Wiegand or Clock Data Readers providing one entry/exit Door or two
entry/exit only doors
Readers (Multiplex-reader
Mode)
4 Wiegand Readers (connected in multiplex reader mode) providing any
combination of entry or exit for two doors
Inputs (System Inputs) 8 High Security Monitored Inputs
Outputs 4 50mA (Max) Open Collector Outputs for reader LED and beeper or general
functions
Relay Outputs 2 FORM C Relays - 7A 250V max
Operating Temperature 0˚-49˚C (32˚ - 122˚F)
Storage Temperature -10˚- 85˚C (14˚ - 185˚F)
Humidity 0%-93% non condensing, indoor use only (relative humidity)
Dimensions (L x W x H) 156 x 90 x 60mm (6.14 x 3.54 x 2.36")
Weight 376g (13.26oz)
* The Total Combined Current refers to the current that will be drawn from the external power supply to supply
the Controller itself as well as any devices connected to the outputs of the Controller. The Auxiliary outputs and
Bell output are directly connected via electronic fuses to the N+ N- input terminals, and the maximum current is
governed by the trip level of these fuses.