Generate Alarms: When enabled the input type will process alarms from the input that it is assigned.
Generate 24HR Alarms: When enabled the input type will process tamper alarms from the input that it is
assigned.
Entry Delay Input: When enabled the input type will start the entry delay timer for the assigned area when
the input generates an alarm.
Entry Delay Follow Input: When enabled the input type will allow this input to generate alarms during the
entry delay however it will generate an alarm if the alarm condition occurs outside the entry delay period.
Exit Delay Input: When enabled the input type will allow this input to generate alarms during the exit delay
however it will generate an alarm if the alarm condition occurs outside the exit delay period. Use this feature
to prevent 'Sitters' from re-entering a building that is assumed to be secure during a long arming process.
Short Exit On Restore: When enabled the input type will shorten the exit delay timer on an area to five
seconds when the input restores. Use this feature to reduce the arming time of an area.
24hr Panic Input: When enabled the input type will generate a 24HR alarm if the input generates an alarm.
The area state will not affect the generation of this alarm.
Fire Input: When enabled the input type will generate a fire alarm when it is activated. This input type will
also operate similar to the 24HR Alarm option. Most smoke detectors use a normally open contact so any
input that is assigned this option must have the inverted state option selected and the EOL resistors option
enabled.
Reporting Options
Report Alarms: When enabled the input type will generate a reportable alarm message.
Report Tampers: When enabled the input type will generate a reportable tamper message.