Specifications

56 PRT-WX-DIN Using Protege WX Installation and Programming Manual | June 2013
Inputs | Options
Options 1
Log to Event Buffer: When enabled, the input will generate an event whenever it is opened, closed,
tampered or shorted. The input will still perform all functions that are programmed if this is not enabled.
When using inputs as automation inputs it is recommended to disable the event logging option to reduce
the impact on the event log buffer.
Test For Trouble Condition: When enabled the input will be monitored for a trouble condition and cause a
trouble alarm to be generated. The trouble will be generated only if the input is either shorted or tampered.
Bypassing Not Allowed: When enabled, the input is a high security input and cannot be bypassed.
However, the input can still be force armed if the Force Arming option is turned on. In order to avoid this,
and to insure that the input is not ignored when force arming, the Input Force Arming option should be
turned off in the input type that is assigned to the input.
Latch Bypassing Not Allowed: When enabled the input is a high security input and cannot be latch
bypassed. However, the input can still be force armed if the Force Arming option is turned on. In order to
avoid this, and to insure that the input is not ignored when force arming, the Input Force Arming option
should be turned off.
Input Inverted: When enabled, the input will operate in an inverted mode. By default all inputs are normally
closed, setting this option will change the input to normally open. At least one input open and close is
needed to correctly update the input state.
Log Input Event when Bypassed: When enabled, the input will generate an event whenever it is bypassed.
Tamper Input if Module Offline: When enabled, the input will operate as a tamper input when the module
is offline.
Options 2
Tamper Follows Bypass State: When enabled the input will bypass the tamper monitoring of the input at
the time the input is bypassed.
No Bypass If Any Area Armed: When enabled the input will be prevented from being bypassed if it is
already assigned to an area that has either the 24HR processing enabled or the area is armed.
Input End of Line (EOL): Defines the resistors used for EOL configuration.