Specifications
PRT-WX-DIN Using Protege WX Installation and Programming Manual | June 2013
55
Address
Module Type: The type of module that the input is attached to.
Module Address Input: The address of the module that the input is attached to.
Module Input: The index of the specified input on that module.
Configuration
Control Output/Output Group: The output that is assigned to the input. This will activate whenever an
input type process's the input with the activate input output options enabled. The input type must have the
appropriate input control output options set in the output options. An output can be assigned to the input
type and to the input allowing many to one and one to many configurations.
Reporting ID: The Input Reporting ID allows the installer to program any reporting number to any input. This
provides an extremely high level of flexibility to assign true reporting numbers to the inputs. An input that is
assigned the same reporting ID as another input will result in both the inputs reporting that ID. If an input is
assigned an ID number that is higher than the maximum number that can be reported by a particular
service, the service will use the maximum number that can be assigned for the format.
Alarm Input Speed: The alarm input speed determines how long an input must be open for before an alarm
event will be generated. This can be set from 0 seconds up to 1 hour. If the Alarm Input Speed is set at 0
seconds, the Restore Input Speed cannot be set below 100ms.
Restore Input Speed: The restore input speed determines how long an input must be closed for before an
restore event will be generated. This can be set from 0 seconds up to 1 hour. If the Alarm Input Speed is set
at 0 seconds, the Restore Input Speed cannot be set below 100ms.
Inputs | Areas and Input Types
Assigned Areas
Area: The input must be assigned to at least one area for it to perform any function in the system and an
input can be assigned in up to 4 different areas. An input can perform a different function in each area which
is defined by the input type. For example an input can be a delay input in one area and an instant input in
another.
Input Type: When an input is assigned to an area the input must be programmed with the type of input (24
Hour Panic, Burglary Delay etc) in order to function.