Specifications

PRT-WX-DIN Using Protege WX Installation and Programming Manual | June 2013
53
Doors | Advanced Options
Advanced Options
Lock out REX When Inside Area Armed: When enabled the door will deny a request to exit when the
inside area has been armed to prevent egress from an armed area.
Deny Entry if Inside Area is Armed: When enabled the door will deny any entry if the inside area is armed.
Deny Exit if Outside Area is Armed: When enabled the door will prevent any exit if the outside area is
armed.
Disable Door Alarms on Schedule Unlock: When enabled the door will not generate the door left open
alarm events to the reader expanders beeper and led ports if they are programmed. This allows a door to
be "propped" open during normal opening times however a pre-alarm warning will still be generated. This
option DOES NOT prevent the door left open trouble input from being sent to the monitoring station if
reporting on the trouble input is programmed to be generated. To prevent the door open alarms from being
sent schedule the input type for the door open alarm events to operate without reporting during the day.
Prompt User For Access Reason Code: When enabled the user will be prompted on the reader
expanders associated keypad to enter their reason for access. The user must enter the reason before
access will be granted.
Enable Access Taken on Door Unlock Events: When enabled the door will generate a User Access Taken
event if the door opens while the door is unlocked after entry has been granted. If the door remains closed
an Access Not Taken event will be generated.
Extended Access Time Options
Door Extended Access Time: The duration (in seconds) that the door remains opens for users tagged as
requiring extended access.