Specifications

PRT-WX-DIN Using Protege WX Installation and Programming Manual | June 2013
51
Left Open Alarm Pulse On Time: The left open alarm pulse on time is used to make the output pulse on
and off when activated. The value entered here must be greater than 0 and is in increments of 100ms. For
example setting 10 will pulse the unit on for 1 second and then off for the programmed time set in the pulse
off section.
Left Open Alarm Pulse Off Time: The left open alarm pulse off time is used to make the output pulse on
and off when activated. The value entered here must be greater than 0 and is in increments of 100ms. For
example setting 10 will pulse the unit off for 1 second and then on for the programmed time set in the pulse
on section.
Door Forced Open Output:
Force Open Output/Output Group: You can assign an output or output group that will activate when the
door is forced open without any access. Use this feature to activate a local output at the door indicating it
has been forced. To generate an alarm on a forced door use the forced door trouble input and assign this
to an area so that a report can be sent to a monitoring station or locally control computer.
Force Open Pulse On Time: The forced open pulse on time is used to make the output pulse on and off
when activated. The value entered here must be greater than 0 and is in increments of 100ms. For example
setting 10 will pulse the unit on for 1 second and then off for the programmed time set in the pulse off
section.
Force Open Pulse Off Time: The forced open pulse off time is used to make the output pulse on and off
when activated. The value entered here must be greater than 0 and is in increments of 100ms. For example
setting 10 will pulse the unit off for 1 second and then on for the programmed time set in the pulse on
section.
Doors | Options