Specifications
PRT-WX-DIN Using Protege WX Installation and Programming Manual | June 2013
49
Doors
Doors are used for the control of access by users or to monitor and control the flow of people in to an area.
Name: The name of the door.
Setup
Door Type: The door type selection allows the door to function in different modes. These modes require
the user to present specific credentials for example a card, card and pin, card or pin and pin only. By using
a door type these can be scheduled dependent on the time of day allowing different security credentials to
be used.
Area Inside Door: The inside area defines which area is on the inside of this door. This is used to prevent a
user from gaining access to a door when the area is armed and they cannot disarm it as well as
automatically disarming the area when the door is accessed. Using the door and area control integrates the
two systems and is an ideal solution to false alarm prevention.
Area Outside Door: The outside area defines which area is on the outside of this door. This is used to
prevent a user from gaining access to a door when the area is armed and they cannot disarm it as well as
automatically disarming the area when the door is accessed. Using an inside and an outside area usually
requires that the door is programmed with both an entry and exit reader.
Unlock Schedule: The unlock schedule determines when this door will unlocked. For example an employee
entry door may require to be unlocked at 7am and locked at 5pm you would assign a suitable schedule
here. Using the unlock on late control option prevents the door unlocking on schedule until the first user
access the door.
Door Pre-Alarm Delay Time: The pre-alarm time is programmed to allow the door to be left open for a
certain period before it will generate a pre-alarm condition. When the pre-alarm condition is reached this will
typically activate an output on the Reader Expander that is controlling the door.
Door Left Open Alarm Time: The maximum door open time when it is reached will generate a door left
open alarm activating the appropriate trouble input and output on the Reader Expander that is controlling
the door. The default configuration will mean that the door will generate a left open alarm 15 seconds after
the pre-alarm condition. For the trouble inputs to activate they must be set in the reader expander.