Specifications
PRT-WX-DIN Using Protege WX Installation and Programming Manual | June 2013
17
The default IP address is set to a static IP address of 192.168.1.2 with a subnet mask of 255.255.255.0. These
IP address settings are commonly used for internal networks. The IP address of the Controller can be
configured using the LCD Keypad terminal or via the built in web interface.
i
Installing the Controller on an active network requires knowledge of the configuration and structure for
the network. Always consult the network or system administrator and ask them to provide you with a
fixed IP address that can be assigned to the Controller.
Connect the Telephone Dialer
If using Contact ID to provide offsite alarm monitoring, connect the telephone line directly to the Controller using
the onboard telephone connection terminals.
Telco line out
Telco line
tip and ring input
R1i T1o R1o
T1i
Telephone Line Connection
Connect Inputs
The Controller has 8 onboard inputs for monitoring the state of devices such as magnetic contacts, motion
detectors and temperature sensors. Devices connected to these inputs can be installed to a maximum distance
of 300m (1000ft) from the Controller when using 22 AWG. The Controller supports normally opened and
normally closed configurations with or without EOL resistors.
When using an input with the EOL resistor configuration, the Controller generates an alarm condition when the
state of an input is toggled and generates a tamper alarm condition when a wire fault (short circuit) or a cut
(tampered) in the line occurs.
Inputs default to require the EOL resistor configuration.
N.C Input Contact
N.C Tamper 1K 1K
V+
V-Z4 V- Z3 Z2 V- Z1
EOL Resistor Input Configuration