Specifications
16 PRT-WX-DIN Using Protege WX Installation and Programming Manual | June 2013
Connect Lock Outputs
The Controller provides a connection for an electric strike lock with full monitoring of the lock circuit for tamper
and over current/fuse blown conditions.
+
-
1N4007 Diode
12VDC Electric
Locking Device
+
-
Power Supply for
Locking Devices
Max 30VDC
V+
V- NO C NC NO C NC
Typical Lock Output Connection
i
The Bell output current must not exceed 1.1A or electronic shutdown will be engaged. Ensure the
devices connected to the outputs are within the limits as described in the Technical Specifications (see
page 7).
Connect the Ethernet 10/100 Network Interface
The Controller comes with an onboard 10/100 Ethernet network interface that is used for IP monitoring and to
connect to the Controller to carry out configuration and monitoring.
When installing, the Controller should be interfaced using a standard segment (<100m in length) and should be
connected to a suitable Ethernet hub or switch.
Ethernet 10/100 Switch hub Connection
Temporary direct connections can be used for onsite programming by connecting directly to the computer
Ethernet port.
Ethernet 10/100 Direct Connection