Specifications
PRT-WX-DIN Using Protege WX Installation and Programming Manual | June 2013
13
End of Line (EOL) Resistors
The 330 Ohm EOL (End of Line) resistor provided in the accessory bag must be inserted between the NA and
NB terminals of the first and last modules on the RS-485 network. These are the modules physically located at
the ends of the RS-485 network cabling.
330R 330R
NAN+ N- NB NAN+ N- NB
First Module on RS-485 Network Last Module on RS-485 Network
To
Next
Module
From
Previous
Module
End of Line Resistors
Connect Card Readers
The Controller provides onboard access control. This enables you to connect two Wiegand devices to control
two doors (entry or exit only), or - if the Controller is configured for multiplex mode - enables you to connect four
Wiegand devices to control two doors giving the flexibility of entry and exit readers, without the need for
additional hardware.
Important:
Card readers must be connected to the Controller port using a shielded cable.
The shield connection must only be connected at one end of the cable in the metallic enclosure
(frame grounded).
Do not connect the shield to a V- connection on the Controller.
Do not join the shield and black wires at the reading device.
Do not connect the shield to any shield used for isolated communication.
Always refer to the card reader manufacturer for detailed installation guidelines.
All Protege Readers are shipped with single LED mode set as default.