Specifications

PRT-WX-DIN Using Protege WX Installation and Programming Manual | June 2013
111
Areas Requiring Rearming due to Input Changes
Typical Health Status Message
Area Warehouse requires rearming due to Input Warehouse PIR changes
Cause
The 24 hour portion of an area must be rearmed when programming changes result in the input functioning in a
different manner. This is to prevent inadvertent changes to a live system that could result in an undetected
security breach.
Solution
1. Navigate to Monitoring | Areas and click Controls to open the manual control window.
2. Click Disarm 24 to disarm 24 hour monitoring, then Arm 24 to enable it.
Areas with the Tamper Area Disarmed
Typical Health Status Message
Area Warehouse has its Tamper Area disarmed
Cause
Every Area created in Protege WX is actually made up of two areas: The main area that monitors devices (such
as PIRs) only when it is armed, and the 24 hour (or Tamper) area that monitors for a tamper or short condition
on devices (such as PIRs) 24/7.
The 24 hour tamper area is armed automatically when the main area is armed.
Solution
1. Navigate to Monitoring | Areas and click Controls to open the manual control window.
2. Click Arm 24 to enable 24 hour monitoring.
Inputs Assigned an Area but no Input Type
Typical Health Status Message
Input Warehouse PIR has an Area but no Input Type assigned
Cause
An input has been assigned to an area, but the system has not been instructed on what to do if the input is
activated.
Solution
1. Navigate to Programming | Inputs and select the input listed in the message
2. Click the Areas and Input Types tab, then select an Input Type from the dropdown
3. Save your changes