Specifications

PRT-WX-DIN Using Protege WX Installation and Programming Manual | June 2013
109
To Set the Network Address of a Module:
1. Ensure the Controller is correctly powered.
2. Connect the module(s) that require addressing to the module network. Make sure that the Power light on
each module is on and that the Status light begins flashing rapidly.
3. Allow some time for the module(s) to attempt to register with the Controller.
If the module has the default address of 254 or has the same address as another module, the Fault
light will begin flashing at 1 second intervals.
If the module has been previously addressed and is not a duplicate, then it will succeed in registering
and the Status light will begin flashing at 1 second intervals.
4. Once all modules have completed the registration process (successful or not), open the Module Addressing
window by selecting Expanders | Expander Addressing
5. Enter an address for the relevant module(s) by selecting an option under the Address column then click
Save to save the address and restart the module.
6. Allow around 5 seconds per module for the new address to be sent and registered then click Refresh to
update the list and display the new addresses.
If the address has not changed, check the module is online and communicating and that is has finished
attempting to register.
If the address has changed but the module is not shown as registered, check the address is in the valid
address range and that it is not a duplicate of another modules address.
Once all modules are online and registered with the desired addresses, the addressing process is complete.