Specifications
106 PRT-WX-DIN Using Protege WX Installation and Programming Manual | June 2013
Upgrading Firmware
From time to time, ICT release new firmware with updates and enhancements to the features included. To
ensure your installation is running at the optimal performance, we recommend that all installed modules utilize
the latest firmware releases.
1. From the main menu, select System | Firmware.
The Firmware page opens containing details about the current firmware version that is installed.
2. Click the Choose File button and browse to the supplied update file.
3. Click Upload Firmware to commence the firmware update procedure.
Progress is shown as the new firmware is installed. Once finished, you will be prompted to cycle power to the
controller. The Controller is then restarted and normal operation is resumed.
i
Note that this process can take up to 5 minutes to complete so we recommend that firmware updates
are performed when the site is closed for maintenance or at times of low activity. The Controller will
not be able to perform it's normal function while firmware is being updated.
Defaulting a Controller
The Controller can be set back to the factory default which resets all internal data and event information. This
allows you to remove all programming and start afresh.
1. Remove power to the Controller by disconnecting the 12V DC input.
2. Connect a wire link between the Reader 2 D0 input and the Reader
2 L1 output.
3. Power up the Controller.
4. Once the Controller has started and the Status light is flashing,
remove the wire link from the Reader 2 connector.
The system will now be defaulted with all programming and settings
returned to factory configuration.
i
Defaulting the Controller does not reset the IP address. Refer to Configuring the IP Address (see page
107) for instructions on how to reset the address.
BZ L1 D1 DO