Specifications

Configuring the Test Station Software Parameters 39
SCOTT SAFETY 087-0048 REV B
To make changes to a particular field, update the value and ensure the Check Box on
the left hand side is checked.
After configuration changes, click WRITE. If a successful write, a Green Bar appears
in the bottom right hand corner of the screen.
High Alarm/Low
Alarm Set Points
Allows adjusting the low/high alarm set point from the factory defaults.
For H
2
S:
Default low/high =10/15PPM
Range =1 to 100 PPM
For CO:
Default low/high =35/100PPM
Range =1 to 300PPM
For O
2
:
Default low/high=19.5/23.5% Volume
Range=1 to 30% Volume
Note: Ensure the set alarm limit do not exceed the local or site
guidelines. Some sites may have different set points than others.
Display Sets detector display; Both, Sensor Reading, or Life Remaining. Both
mode shows life remaining instead of zero. When it’s not reading zero,
then it shows the gas reading.
Default= Both
Hide Bump Due
LED Flashing
When checked, disables the monitor from flashing when due for a Bump
Test.
When unchecked, the monitor flashes when due for a Bump Test.
Default= Unchecked
Note: Ensure all applicable Check Boxes are marked to enable this
function. The one to the left and under the applicable Sensor Type.
Firmware Upgrade Allows Firmware upgrades during the life of the Test Station. These
may be product improvements to add additional features or to enhance
monitors performance. Most firmware upgrades are not required unless
notified by us. To see if your Test Station has the most current version,
please contact us.
Note: Once new firmware is upgraded to the Test Station, monitors are
upgraded before testing. During the upgrade, the Test Station’s LEDs
remain Orange and Flash. Do not move the monitor during a firmware
upgrade.
Table 14 Test Station Protege ZM Tab Parameters (continued)
ITEM DETAILS