38 CHAPTER 4: CONFIGURATION AND SETUP
087-0048 REV B SCOTT SAFETY
Warning: Avoid setting the High Alarm parameter to a value that is lower than the
Low Alarm parameter or vise vera. Also, avoid setting either or both High and Low
Alarms parameters to zero. Failure to follow these instructions may result in serious
injury or death.
Figure 29 Test Station Software Protege ZM Tab Screen
Table 14 Test Station Protege ZM Tab Parameters
ITEM DETAILS
User ID Used to assign a unique electronic user ID.
Range= Up to 6 characters.
Note: Tab down to this field to select prior to entering ID. Otherwise
field will not accept entry. Also, some alphabetic characters do not
display well on the segmented display.
Calibration
Interval
Sets the time between calibrations
Bump Interval Setting a value automatically displays BUP on the monitors LCD when
the monitor has not been Bump Tested within the time frame and
remains until cleared. This option aids in bump test accountability.
Default=0
Range=0 to 365 days.
For details on clearing this parameter, See “Clearing a Bump Test
Interval Alarm Alert” on page 61.
Self Test Interval Allows adjusting the self test frequency from the default.
Default=20
Range=6 to 24 hours