Specifications
84 PRT-CTRL-SE Protege System Controller Reference Manual | PRT-CTRL-SE
Analog Expander
To access the Analog Expander module programming, login using a valid installer code and then select [MENU,
4, 1, 5]. The screen displays "Analog exp to modify" as shown in the following example.
Analog Exp to
modify: AE001
Every time you press the Enter key, the next screen appears. The different screens are described in the
following sub-sections. Programming the Analog Expander allows you to set the polling time of the module,
channel options and the configuration of the differential settings if they are used.
When programming module some options are processed at the module, for these options to operate correctly a
network reload or update must be performed and the analog expander must be registered and online.
Updating modules can be accessed by selecting [MENU, 4, 8, 1, 3], reload and restart the module by pressing
the [MENU, 4, 8, 1, 4], you can also check the status of your modules by selecting [MENU, 4, 8, 1, 1] for all
modules presently offline and [MENU, 4, 8, 1, 2] for all online modules. For more information refer to the
Advanced Menu section (see page 201).
Selecting an Analog Expander to Modify
Each analog expander is assigned a unique address from 001 to 250. Configuring the address of the Analog
Expander Module (PRT-ADC4 or PRT-DAC4) is covered in the installation instructions included with your
PRT-ADC4 Analog Input Expander or PRT-DAC4 Analog Output Expander Module.
Analog Exp to
modify: AE001
Type the appropriate 3-digit Analog Expander address or use the [Ð] and [Ï] keys. When the desired address
appears on the screen, press [ENTER] to program the selected Analog Expander module. The maximum
number of Analog Expanders that can be programmed is limited by your system's memory and configured
profile.
Displaying Selected Analog Expander Information
It is possible to show the current Analog Expander registration and information details (module type PRT-ADC4
or PRT-DAC4, registration, online and version information) from the Analog Expander selection display.
Analog Exp to
modify: AE001
Type the appropriate 3-digit Analog Expander address or use the [Ð] and [Ï] keys. When the desired address
appears on the screen, press the [ARM] key to display information on the selected Analog Expander. The
screen will now display information about the Analog Expander that was selected. Press any other key to return
to the Analog Expander selection window.
11-14-72-B9 [23]
V 1.05 2404 A RO
The display above represents the following information for the selected keypad:
11-14-72-B9 Serial Number of the registered 2 Analog Expander at the selected address.
[23] The current polling timeout value.
V 1.05 Software version of the registered analog expander.
2404 Software version build number.
A This means an Analog Input (PRT-ADC4) is at this location
a 'D' would indicate an Analog Output (PRT-DAC4) module had been registered.
R The Analog expander is registered.
('*' will indicate no expander registered)
O The Analog expander is online.
('*' will indicate the expander is offline)