Specifications
PRT-CTRL-SE Protege System Controller Reference Manual | PRT-CTRL-SE 83
Option 1 – Invert Floor Relays
y Enabled the reader expander will invert all the relays on the PX16's connected that are used for elevator
control.
y Disabled the reader will not invert the relays.
Option 2 – Control on Comm Fail
y Enabled the PX16 used for elevator control will control the state of the relays when they go offline. Option
3 determines the state the relays will go into.
y Disabled the PX16 used for elevator control will not change the state of the relays when they go offline..
Option 3 – Activate on Comm Fail
y Enabled the PX16 will activate the relays when they go offline.
y Disabled the PX16's will deactivate the relays when they go offline.
Option 4 - 8 - Reserved
y Reserved do not modify
Reader Port 2 Function PGM
You can assign a PGM or PGM group that is used by the multiple badge options.
RD001 R2 Func
pgm: --000:00
To modify the PGM or PGM Group, use the settings as explained in section Entering PGM and PGM Groups
(see page 336).
Reader Communication Failure Card Reading Operation
When the reader expander fails to communicate with the system controller it will default to allowing access
through the controlled doors based on the offline communication failure configuration and the type of module
that has been registered at the reader location. An intelligent reader expander device will always process users
based on the internal offline database and the configuration settings have no affect unless the No Cards option
is selected.
RD001 Offline
All Cards
Option Function
No Cards Setting no cards will prevent ANY access from a card reader in the event the module fails
and goes offline. This is also applicable to the PRT-RDI2 and PRT-RDE2 modules.
All Cards This will allow ANY card to enter a reader on the PRT-RDM2 and PRT-RDS2 however on
the PRT-RDI2 and PRT-RDE2 only cards that have the correct access credentials
according to the internal database at the module will be allowed access.
First Ten This will allow UN00001 to UN00010 to have unlimited access to the reader inputs on the
PRT-RDM2 and PRT-RDS2 however on the PRT-RDI2 and PRT-RDE2 only cards that
have the correct access credentials according to the internal database at the module will
be allowed access.
Site Code During the operation of the PRT-RDM2 and PRT-RDS2 the application will store the site
codes of cards that have been granted access to the door, the site code will be cached
for a period of 7 days or until the card is denied access normally. Setting this option will
allow ANY card with the same site code to access the readers on the PRT-RDM2 and
PRT-RDI2 modules. The PRT-RDI2 and PRT-RDE2 only cards that have the correct
access credentials according to the internal database at the module will be allowed
access.
Use the [1] and [3] keys to scroll the available offline communication settings. For more information about the list
control data entry refer to the section List Control Data Entry (see page 335).