Specifications

82 PRT-CTRL-SE Protege System Controller Reference Manual | PRT-CTRL-SE
Option 6 - Request To Exit Operates Always
y Enabled the reader will always allow a request to exit event EVEN if the door is forced open. This will not
restart the forced door or the door alarm operation.
y Disabled REX input will operate only when the door is closed.
Option 7 - Recycle Door Open Too Long Timer On Request To Exit Operation
y Enabled the reader will extend the door open time when the REX is received. The REX must be received
during the normal open time or during the pre-alarm time for the timer to be recycled. Pressing the request
to exit once the door open too long has been entered will require the door to be closed. This option will not
affect the ability for the request to exit action to unlock the door.
y Disabled REX input will not alter the door open time once the door as been opened.
Option 8 - Reserved
y Reserved do not modify
Reader Port 2 Process Options
Options that relate to the extra reader functions.
RD001 R2 Process
[--------]
To modify options, use the keypad as explained in section Entering Data Options (see page 336).
Option 1 – Convert Force to Door Open
y Enabled the reader expander will process door forced open events as door open events.
y Disabled the reader will process forced door events as normal.
Option 2 – Disable Red LED Processing
y Enabled the reader expander will not control the Red LED (L2) and the PGM can be used for another
function, this is particularly useful if the attached proximity reader LED's is controlled with one wire.
y Disabled the reader will turn on the Red LED when the door is locked.
Option 3 – Disable Green LED Processing
y Enabled the reader expander will not control the Green LED (L1) and the PGM can be used for another
function, this is particularly useful if the attached proximity reader LED's is controlled with one wire.
y Disabled the reader will turn on the Green LED when the door is unlocked.
Option 4 – Disable Buzzer Processing
y Enabled the reader expander will not control the Buzzer Output (BZ) and the PGM can be used for another
function.
y Disabled the reader will control the buzzer output.
Option 5 - 8 - Reserved
y Reserved do not modify
Reader Port 2 Elevator Options
Options that relate to the elevator functions.
RD001 R2 Elv Opt
[--------]
To modify options, use the keypad as explained in section Entering Data Options (see page 336).