Option 5 - Request To Exit (REX) Enabled
y Enabled the reader expander will generate request to exit events from the REX input on the reader
expander.
y Disabled the keypad will not generate any REX events.
Option 6 - Request To Enter (REN) Enabled
y Enabled the reader expander will generate request to enter events from the REN input on the reader
expander.
Option 7 - Generate Format Error Events
y Enabled the reader expander will send a detailed format error to the system controller if it receives
information from the reader that does not comply with the programmed format. Format errors include bit
count, byte count, parity, checksum and LRC calculation failures.
y Disabled the reader will silently discard any format error. The format error will still be indicated on the reader
input data LED.
Option 8 - Intelligent Reader Tamper
y Enabled the reader expander will assume that the external device has smart messaging that allows a
communication path to be formed from the reading device (Card Reader) to the reader expander.
This allows the reader expander to monitor the reading device and generate a reader missing alarm (Trouble
Zone) if it fails to communicate with the reader expander allowing the failure to be reported to a monitoring
station.
y Disabled the intelligent reader mode is disabled.
Reader Port 2 Miscellaneous Options
Options that relate to the miscellaneous reader functions.
RD001 R2 Misc
[--------]
To modify options, use the keypad as explained in section Entering Data Options (see page 336).
Option 1 - Disarm Area
y Enabled the reader process will disarm the area designated by the reader type (ENTRY or EXIT) and the
door configuration programmed (If it has an area on the inside or outside assigned).
If this option is enabled and the reader is only used for area control then the area disarmed will be the area
assigned in the area control setting.
y Disabled the reader will not perform any disarm functions.
Option 2 – Allow User Access if Area Armed
y When the option is enabled the user will be granted access based on the access control configuration only
and the area status will not be checked against the user's ability to disarm the area.
y When the option is disabled and the user who is attempting access to a door that has an area assigned that
is armed and the user can not disarm the area the user will be denied entry to the door even though they
may have the correct door and schedule settings.
Option 3 - Disarm User Area
y Enabled the reader will disarm the user's area when access is granted to the door they are attempting to
access. The users area must still be available in the user area group assigned to the users access level.
y Disabled the reader will not perform any user area functions.
Option 4 - Generate Reader Events
y Enabled the reader events will be logged to the event review log.
y Disabled the reader will not log the events to the event review log.