Specifications
PRT-CTRL-SE Protege System Controller Reference Manual | PRT-CTRL-SE 79
Mode Operation
None No action will be taken by the system for arming an area associated with the door.
Arm on 2 Reads Two successive reads from the same user will result in the inside or outside area
(depending on the card reader type configuration) starting the arming process.
Arm on Card Read and
Zone Input 8
Pressing and holding Zone Input 8 (RDXXX:08) while presenting a card will begin
arming. Zone 8 must be in an area that is armed to ensure the zone information is
transmitted to the system controller. The area armed will depend on the card
reader type setting.
Arm on 3 Reads Three successive reads from the same user will result in the inside or outside area
(depending on the card reader type configuration) starting the arming process.
Toggle Function PGM Three successive reads from the same user will result in the function PGM state
being toggled. If the PGM is currently on it will be turned off and if it is off it will be
turned on.
Activate Function PGM Three successive reads from the same user will result in the function PGM state
being turned on
Reader Port 2 Reader Options
Options that relate to the control of reader functions.
RD001 R2 Option
[123-5---]
To modify options, use the keypad as explained in section Entering Data Options (see page 336).
Option 1 - Reader On Unlock and Door Open
y Enabled the reader expander will send card information to the system controller when a door is unlocked or
opened. This option is set by default and should be left set if the door controls areas or time and attendance
events are required from the reader port
y Disabled the reader performs no action when a card is presented and the door is unlock or open.
Option 2 - Send Door Monitoring Events
y Enabled the reader will send door events when the door input is opened or closed. This is enabled by
default but should be disabled on at least one reader port if both reader ports are controlling the same door
(ENTRY and EXIT access control).
y Disabled the reader expander will not send any door events.
Option 3 - LED Follow Lock Status
y Enabled the reader will activate the LED outputs on the reader expander when the lock is opened. This
option DOES not prevent the outputs from being used to display the area armed or alarm status.
y Disabled the reader will not perform any function on the LED outputs.
Option 4 - Bond Sense Input Enable
y Enabled the magnetic bond sense functions. The magnetic bond sense is a contact that indicates if the
magnetic bond between the electromagnet and the clamp is complete. It is used when a separate door
contact and bond sense input are to be used however the generation of door events should be processed
using both inputs.
When opening either of the two contacts open (Door Contact or Bond Sense Input) the door monitoring will
see this as the door being opened and process it accordingly.
y Disabled the reader will not include the bond sense input in the door status processing.