Specifications

PRT-CTRL-SE Protege System Controller Reference Manual | PRT-CTRL-SE 77
Reader Port 2 Elevator Car
The reader elevator car is used when the reader port 2 mode of operation is configured for Elevator Control
mode. When configuring the elevator control mode you must also configure the elevator number for the reader
expander that the floor control relays are located on, this is typically the same reader expander that the card
reader is connected to. For information on programming the elevator car refer to the Elevator Programming
Section (see page 141).
RD001 R2 ElvNum
None
Use the [1] and [3] keys to scroll the available elevators. For more information about the list control data entry
refer to the section List Control Data Entry (see page 335).
Reader Port 2 Reading Format
The reading format is used to inform the reader expander what type of card readers are connected to the reader
port one. The reader expander supports nearly all publicly available protocols and some special protocols. Any
26 or 37 bit card reader that conforms to the standard format specification will work on the PRT-RDI2 Reader
Expander.
RD001 R2 Format
26 Bit
Use the [1] and [3] keys to scroll the available card reader format settings. For more information about the list
control data entry refer to the section List Control Data Entry (see page 335).
For a list of supported formats refer to the Reader Expander Format Table (see page 67).
Reader Port 2 Secondary Reading Format
The secondary reading format is used to program an alternate format for the reader expander and has the same
options as the standard reader selection. The secondary format will only be used if the first format can not
decode the card information that is received by the reader interface.
RD001 R2 Format
None
Use the [1] and [3] keys to scroll the available card reader format settings. For more information about the list
control data entry refer to the section List Control Data Entry (see page 335).
For a list of supported formats refer to the Reader Expander Format Table (see page 67).
Reader Port 2 Reader Type
The reader type informs the reader expander which location of the door the reader is installed that is connected
to the reader expander port two. The reader expander uses this information to pass the correct direction of
travel to the door control functions. For an access door this should be set to ENTRY reader.
When using the reader with a door that controls an inside or outside area or is used for card or key global
anti-passback the ENTRY and EXIT configuration must be set correctly.
RD001 R2 Type
ENTRY Reader
Use the [1] and [3] keys to scroll the available reader type settings. For more information about the list control
data entry refer to the section List Control Data Entry (see page 335).