Specifications

76 PRT-CTRL-SE Protege System Controller Reference Manual | PRT-CTRL-SE
Reader Port 1 Function PGM
You can assign a PGM or PGM group that is used by the multiple badge options.
RD001 R1 Func
pgm: --000:00
To modify the PGM or PGM Group, use the settings as explained in section Entering PGM and PGM Groups
(see page 336).
Reader Port 2 Mode
The reader mode setting determines what function the reader attached to port two will perform.
RD001 R2 Mode
Access
Use the [1] and [3] keys to scroll the reader mode settings. For more information about the list control data entry
refer to the section List Control Data Entry (see page 335).
Operating Mode Operation
Access The reader expander port is used to control access through doors. You must configure
the door that is controlled by this reader expander. This mode should also be used if
control of a lobby or elevator call button is required. To control a elevator car use the
Elevator Mode.
Elevator The reader expander is used to control access to floors within an elevator. You must
configure the elevator number that is connected to the reader.
Area Control The reader expander input is used to ONLY control an area for arming and disarmed.
Please note that this can be achieved using the Access Mode as well by integrating the
alarm and access control systems.
Reader Port 2 Controlled Door
The reader controlled door setting sets the door that the reader on port two will provide card and control
information to. It is possible that more than one reader has the same controlled door (Entry and Exit reading
configuration).
RD001 R2 Door
None
Use the [1] and [3] keys to scroll the available door settings. For more information about the list control data
entry refer to the section List Control Data Entry (see page 335).
Reader Port 2 Controlled Area
The reader controlled area setting sets the area that the reader on port two will control if the reader mode is set
as area control. If area control is selected the reader can not be used for other functions. If you want to disarm
and arm areas and gain access to doors refer to the Reader Misc Options section (see page 73).
RD001 R2 Area
None
Use the [1] and [3] keys to scroll the available area settings. For more information about the list control data
entry refer to the section List Control Data Entry (see page 335).