Specifications
PRT-CTRL-SE Protege System Controller Reference Manual | PRT-CTRL-SE 75
Reader Port 1 Process Options
Options that relate to the extra reader functions.
RD001 R1 Process
[--------]
To modify options, use the keypad as explained in section Entering Data Options
(see page 336).
Option 1 – Convert Force to Door Open
y Enabled the reader expander will process door forced open events as door open events.
y Disabled the reader will process forced door events as normal.
Option 2 – Disable Red LED Processing
y Enabled the reader expander will not control the Red LED (L2) and the PGM can be used for another
function, this is particularly useful if the attached proximity reader LED's is controlled with one wire.
y Disabled the reader will turn on the Red LED when the door is locked.
Option 3 – Disable Green LED Processing
y Enabled the reader expander will not control the Green LED (L1) and the PGM can be used for another
function, this is particularly useful if the attached proximity reader LED's is controlled with one wire.
y Disabled the reader will turn on the Green LED when the door is unlocked.
Option 4 – Disable Buzzer Processing
y Enabled the reader expander will not control the Buzzer Output (BZ) and the PGM can be used for another
function.
y Disabled the reader will control the buzzer output.
Option 5 - 8 - Reserved
y Reserved do not modify
Reader Port 1 Elevator Options
Options that relate to the elevator functions.
RD001 R1 Elv Opt
[--------]
To modify options, use the keypad as explained in section Entering Data Options (see page 336).
Option 1 – Invert Floor Relays
y Enabled the reader expander will invert all the relays on the PX16's connected that are used for elevator
control.
y Disabled the reader will not invert the relays.
Option 2 – Control on Comm Fail
y Enabled the PX16 used for elevator control will control the state of the relays when they go offline. Option
3 determines the state the relays will go into.
y Disabled the PX16 used for elevator control will not change the state of the relays when they go offline..
Option 3 – Activate on Comm Fail
y Enabled the PX16 will activate the relays when they go offline.
y Disabled the PX16's will deactivate the relays when they go offline.
Option 4 - 8 - Reserved
y Reserved do not modify