Specifications
PRT-CTRL-SE Protege System Controller Reference Manual | PRT-CTRL-SE 63
PGM Expander Module Options
Options that relate to the PGM expander module can be set using option entry.
PX001 Module
[--------]
To modify options, use the keypad as explained in section Entering Data Options (see page 336).
Option 1 - High Current Charging
y Enabled the high current charging option will set 700mA charging in the power supply system.
For PGM expanders that do not have a power supply this option performs no function.
y Disabled the high current option will set the standard 350mA charging rate in the power supply system.
Option 2 – Invert Module Tamper
y Enabled the PGM expander will invert the module tamper input allowing a normally open (door closed)
tamper switch to be used.
y Disabled the PGM expander will use the standard normally closed (door closed) tamper switch.
Option 3 – Stage PGM On/Off
y Enabled the PGM expander will not activate any two local PGMs within 50ms of each other. E.g. If PGM's
1 to 4 were activated at the same time the PX16 would activate PGM 1 first then delay 50ms and activate
PGM 2, continuing like this until all 4 PGMs were activated.
y Disabled the PGM expander will turn on or off all PGM's instantly.
Option 4, 5, 6, 7 and 8 - Reserved
y Reserved do not modify
Reader Expander
To access the Reader Expander module programming login using a valid installer code and then select [MENU,
4, 1, 3]. The screen displays "Reader exp to modify" as shown in the following example.
2 Reader Exp to
modify: RD001
Every time you press the Enter key, the next screen appears. The different screens are described in the
following sub-sections. Programming the Reader Expander allows you to set the polling time of the module,
power supply options and the configuration of the readers with associated doors.
When programming modules some options are processed at the module, for these options to operate correctly
a network update must be performed and the zone expander must be registered and online.
Updating modules can be accessed by selecting [MENU, 4, 8, 1, 3], you can also check the status of your
modules by selecting [MENU, 4, 8, 1, 1] for all modules presently offline and [MENU, 4, 8, 1, 2] for all online
modules. For more information refer to the Advanced Menu section (see page 201).
Selecting a Reader Expander to Modify
Each Reader expander is assigned a unique address from 001 to 250. Programming the address of the Reader
Expander Module (PRT-RDI2, PRT-RDM2, PRT-RDS2 and PRT-RDE2) is covered in the installation instructions
included with your Reader Expander Module.
2 Reader Exp to
modify: RD001
Type the appropriate 3-digit Reader Expander address or use the [Ð] and [Ï] keys. When the desired address
appears on the screen, press [ENTER] to program the selected Reader Expander module. The maximum
number of Reader Expanders that can be programmed is limited by your system's memory and configured
profile.