Specifications
62 PRT-CTRL-SE Protege System Controller Reference Manual | PRT-CTRL-SE
Displaying Selected 16 PGM Expander Information
It is possible to show the current 16 PGM Expander registration and information details (registration, online and
version) from the 16 PGM expander selection display.
16 PGM Exp to
modify: PX001
Type the appropriate 3-digit 16 PGM Expander address or use the [Ð] and [Ï] keys. When the desired address
appears on the screen, press the [ARM] key to display information on the selected 16 PGM Expander. The
screen will now display information about the 16 PGM Expander that was selected. Press any other key to
return to the 16 Zone Expander selection window.
11-14-72-B9 [23]
V 1.05 2404 RO
The display above represents the following information for the selected keypad:
11-14-72-B9 Serial Number of the registered keypad at this address.
[23] The current polling timeout value.
V 1.05 Software version of the registered keypad.
2404 Software build number.
R The PGM expander is registered
('*' will indicate no expander registered)
O The PGM expander is online
('*' will indicate the expander is offline)
To view the IP address of the module press the [Ï] key from this view. If the module is connected over the
RS-485 LAN "---.---.---.---" will be displayed.
To list all offline or online modules refer to the Module Network Functions (see page 201).
Special functions are provided to update and update reset a module individually by using a shortcut key directly
from the keypad selection screen.
Key Function
[STAY] Pressing the [STAY] key will update the PGM expander number that is currently
displayed in the module selection window. This will program the module WITHOUT
resetting the module.
[FORCE] Pressing the [FORCE] key will update and init the PGM expander number that is
currently displayed in the module selection window. This will program the module and
then restart the module.
Module Polling Time
The polling time defines how often the PGM expander module checks in with the Protege System Controller. If a
PGM expander fails to check in, it triggers its associated communication failure trouble zone (PXxxx:08) and the
trouble zone for a general module communications failure.
To enter a polling time (008 to 250 seconds), use the keypad as explained in section Entering Decimal Numbers
(see page 333) and press [ENTER]. By default the PGM expander polling time is set to 250 seconds. Setting a
polling time below 60 seconds should only be done for PGM expanders that are in a non-secure area.
PX001 Polling
time: 250 secs
i
For UL and ULC listed installations you MUST set the polling time to 180 seconds or less.