Specifications

PRT-CTRL-SE Protege System Controller Reference Manual | PRT-CTRL-SE 61
Option 2 - Bell Over Current Requires Acknowledge
y Enabled the bell over current condition will remain until the trouble condition is acknowledged in the system
controller at which point all bells (if more than one bell has a problem) will be cleared and reset.
i
When installing a system to conform to UL or ULC requirements this option must be enabled.
y When the option is disabled and a bell over current condition occurs the bell output will be turned off. It will
be turned on one minute later, if the problem still exists it will be turned off again, this process is repeated
until the bell is deactivated by the area or other function within the system.
Option 3 – Use Alternate Resistors
y Enabled the zone expander will use alternate EOL configured resistors (2K2 and 6K8).
y Disabled the zone expander will use the normal 1K and 1K resistor configuration.
Option 4 – Invert Module Tamper
y Enabled the zone expander will invert the module tamper input allowing a normally open (door closed)
tamper switch to be used.
y Disabled the zone expander will use the standard normally closed (door closed) tamper switch.
Option 5, 6, 7 and 8 - Reserved
y Reserved do not modify
PGM Expander
To access the PGM Expander module programming login using a valid installer code and then select [MENU, 4,
1, 3]. The screen displays "PGM exp to modify" as shown in the following example.
16 PGM Exp to
modify: PX001
Every time you press the Enter key, the next screen appears. The different screens are described in the
following sub-sections. Programming the PGM Expander allows you to set the polling time of the module and
power supply options.
When programming modules some options are processed at the module, for these options to operate correctly
a network update must be performed and the zone expander must be registered and online.
Updating modules can be accessed by selecting [MENU, 4, 8, 1, 3], you can also check the status of your
modules by selecting [MENU, 4, 8, 1, 1] for all modules presently offline and [MENU, 4, 8, 1, 2] for all online
modules. For more information refer to the Advanced Menu section (see page 201).
Selecting a PGM Expander to Modify
Each PGM expander is assigned a unique address from 001 to 250. Programming the address of the PGM
Expander Module (PRT-PG16) is covered in the installation instructions included with your PRT-PG16 PGM
Expander Module.
16 PGM Exp to
modify: PX001
Type the appropriate 3-digit PGM Expander address or use the [Ð] and [Ï] keys. When the desired address
appears on the screen, press [ENTER] to program the selected PGM Expander module. The maximum number
of PGM Expanders that can be programmed is limited by your system's memory and configured profile.