Specifications
60 PRT-CTRL-SE Protege System Controller Reference Manual | PRT-CTRL-SE
The display above represents the following information for the selected keypad:
92-A8-90-C2 Serial Number of the registered keypad at this address.
[9F] The current polling timeout value.
V 1.04 Software version of the registered keypad.
1833 Software build number.
R The expander is registered
('*' will indicate no expander registered)
O ('*' will indicate the expander is offline)
To view the IP address of the module press the [Ï] key from this view. If the module is connected over the
RS-485 LAN "---.---.---.---" will be displayed.
To list all offline or online modules refer to the Module Network Functions (see page 201).
Special functions are provided to update and update reset a module individually by using a shortcut key directly
from the keypad selection screen.
Key Function
[STAY] Pressing the [STAY] key will update the zone expander number that is currently
displayed in the module selection window. This will program the module WITHOUT
resetting the module.
[FORCE] Pressing the [FORCE] key will update and init the zone expander number that is currently
displayed in the module selection window. This will program the module and then restart
the module.
Zone Expander Polling Time
The polling time defines how often the Zone Expander checks in with the Protege System Controller. If a Zone
Expander fails to check in, it triggers its associated communication failure trouble zone (ZXxxx:08) and the
trouble zone for a general module communications failure.
To enter a polling time (008 to 250 seconds), use the keypad as explained in section Entering Decimal Numbers
(see page 333) and press [ENTER]. By default the Zone Expander polling time is set to 250 seconds. Setting a
polling time below 60 seconds should only be done for zone expanders that are in a non-secure area.
ZX001 Polling
time: 250 secs
i
For UL and ULC listed installations you MUST set the polling time to 180 seconds or less.
Zone Expander Module Options
Options that relate to the zone expander module can be set using option entry.
ZX001 Module
[--------]
To modify options, use the keypad as explained in section Entering Data Options (see page 336).
Option 1 - High Current Charging
y Enabled the zone expander will enable 700mA charging in the power supply system.
y Disabled the zone expander will enable 350mA charging in the power supply system.