Specifications

PRT-CTRL-SE Protege System Controller Reference Manual | PRT-CTRL-SE 313
Trouble Zone Maps
Following is a list of all the trouble zones assigned to each of the Protege System modules. Trouble zones are
used to monitor the status of the Protege System and are linked to communication failures, power supply
conditions and enclosure tamper inputs.
In many cases the actual trouble zone is not physically connected to an external device, for example a module
communication failure trouble zone will open when a module fails to send a poll event to the Protege System
controller, the trouble zone will restore when the module returns back online.
Trouble zones are a very powerful programming tool within the Protege System that gives you absolute control
over your system and how the monitoring and presentation of system trouble conditions function.
Control Panel
The following lists the trouble zones that operate on the control panel. The control panel has 64 trouble zones.
Trouble zones that are reserved should not be included in an area.
Zone Number Description Type Group
CP001:01 Module Tamper System Tamper System
CP001:02 AC failure Power Fault General
CP001:03 Low Battery Power Fault General
CP001:04 Real Time Clock Not Set RTC/Clock Loss General
CP001:05 Service Report Test * *
CP001:06 Service Report Failure To Communicate Reporting Failure General
CP001:07 Phone Line Fault Phone Line Lost General
CP001:08 Auxiliary Failure Power Fault General
CP001:09 Bell 1 Cut/Tamper Bell/PGM Fault General
CP001:10 Bell 2 Cut/Tamper Bell/PGM Fault General
CP001:11 Bell 1 Over Current Bell/PGM Fault General
CP001:12 Bell 2 Over Current Bell/PGM Fault General
CP001:13 Module Communication Module Loss System
CP001:14 Module Network Security Module Security System
CP001:15 Expansion Device Missing Hardware Fault System
CP001:16 Communication Port 1 Fault Hardware Fault System
CP001:17 Communication Port 2 Fault Hardware Fault System
CP001:18 Communication Port 3 Fault Hardware Fault System
CP001:19 Communication Port 4 Fault Hardware Fault System
CP001:20 Ethernet Link Lost Hardware Fault System
CP001:21 DVAC Line Fault/Polling Error Hardware Fault System
CP001:22 ModBUS Communication Fault Hardware Fault System
CP001:23 Protege Access Hardware Fault System
CP001:24 Installer Logged In Hardware Fault System