Specifications

294 PRT-CTRL-SE Protege System Controller Reference Manual | PRT-CTRL-SE
Zone Number Contact ID Code Reporting Point Number
ZX001:05 321 (Siren/Bell 1 Tamper) 585
ZX001:06 322 (Siren/Bell 2 Tamper) 586
ZX001:07 312 (Siren/Bell 1 Over Current) 587
ZX001:08 312 (Siren/Bell 2 Over Current) 588
ZX001:09 140 (General Alarm) 589
ZX001:10 140 (General Alarm) 590
ZX001:11 140 (General Alarm) 591
ZX001:12 140 (General Alarm) 592
ZX001:13 140 (General Alarm) 593
ZX001:14 140 (General Alarm) 594
ZX001:15 140 (General Alarm) 595
ZX001:16 143 (Module Offline) 596
ZX002:01 145 (Module Tamper) 597
| | | | | | | |
ZX020:16 143 (Module Offline) 900
ZX021:01 145 (Module Tamper) 999
| | | | | | | |
ZX250:16 143 (Module Offline) 999
In the above table a reporting code of 999 indicates that the trouble zone is outside the maximum trouble zones
that can be reported for the module type.
2 Reader Expander
The 2 reader expander will report trouble zones from 1 to 16 on the first 2 modules, all modules above address
RD002 will be reported using the default code of 999.
Zone Number Contact ID Code Reporting Point Number
RD001:01 145 (Module Tamper) 901
RD001:02 301 (AC Loss) 902
RD001:03 302 (Low System Battery) 903
RD001:04 312 (Auxiliary Fuse) 904
RD001:05 312 (Lock Trouble) 905
RD001:06 423 (Door 1 Forced) 906
RD001:07 423 (Door 2 Forced) 907
RD001:08 426 (Door 1 Left Open) 908
RD001:09 426 (Door 2 Left Open) 909
RD001:10 312 (Reader 1 Power Supply) 910
RD001:11 312 (Reader 2 Power Supply) 911
RD001:12 145 (Reader 1 Tamper) 912