Specifications
PRT-CTRL-SE Protege System Controller Reference Manual | PRT-CTRL-SE 293
Zone Number Contact ID Code Reporting Point Number
CP001:28 415 (Service 4 Stopped) 528
CP001:29 140 (General Alarm) 529
| | | | | | | | | | |
CP001:64 140 (General Alarm) 564
In the above table a reporting code of 999 indicates that the zone is outside the maximum zones that can be
reported in some cases the zone number will reflect the module address that the zone was activated from to aid
in service.
Keypad Zones
The keypad will report trouble zones from 1 to 8 on the first 2 modules, all modules above address KP002 will
be reported using the default code of 999.
Zone Number Contact ID Code Reporting Point Number
KP001:01 145 (Module Tamper) 565
KP001:02 302 (Low Voltage) 566
KP001:03 120 (Panic 1+3) 567
KP001:04 121 (Duress Code) 568
KP001:05 423 (Forced Access) 569
KP001:06 426 (Door Open) 570
KP001:07 461 (Invalid Code Lockout) 571
KP001:08 143 (Module Offline) 572
KP002:01 145 (Module Tamper) 573
KP002:02 302 (Low Voltage) 574
| | | | | | | |
KP002:08 143 (Module Offline) 580
KP003:01 145 (Module Tamper) 999
| | | | | | | |
KP250:04 143 (Module Offline) 999
In the above table a reporting code of 999 indicates that the zone is outside the maximum zones that can be
reported for the module type.
16 Zone Expander
The 16 zone expander will report trouble zones from 1 to 16 on the first 20 modules, all modules above address
ZX020 will be reported using the default code of 999.
Zone Number Contact ID Code Reporting Point Number
ZX001:01 145 (Module Tamper) 581
ZX001:02 301 (AC Loss) 582
ZX001:03 302 (Low System Battery) 583
ZX001:04 312 (Auxiliary Fuse) 584