Specifications
286 PRT-CTRL-SE Protege System Controller Reference Manual | PRT-CTRL-SE
In the above table a reporting code of 999 indicates that the zone is outside the maximum zones that can be
reported in some cases the zone number will reflect the module address that the zone was activated from to aid
in service.
Keypad Zones
The keypad will report trouble zones from 1 to 8 on the first 6 modules, all modules above address KP006 will
be reported using the default code of 999.
Zone Number Contact ID Code Reporting Point Number
KP001:01 145 (Module Tamper) 565
KP001:02 302 (Low Voltage) 566
KP001:03 120 (Panic 1+3) 567
KP001:04 121 (Duress Code) 568
KP001:05 423 (Forced Access) 569
KP001:06 426 (Door Open) 570
KP001:07 461 (Invalid Code Lockout) 571
KP001:08 143 (Module Offline) 572
KP002:01 145 (Module Tamper) 573
KP002:02 302 (Low Voltage) 574
| | | | | | | |
KP006:08 143 (Module Offline) 612
KP007:01 145 (Module Tamper) 999
| | | | | | | |
KP250:04 143 (Module Offline) 999
In the above table a reporting code of 999 indicates that the zone is outside the maximum zones that can be
reported for the module type.
16 Zone Expander
The 16 zone expander will report trouble zones from 1 to 16 on the first 4 modules, all modules above address
ZX004 will be reported using the default code of 999.
Zone Number Contact ID Code Reporting Point Number
ZX001:01 145 (Module Tamper) 613
ZX001:02 301 (AC Loss) 614
ZX001:03 302 (Low System Battery) 615
ZX001:04 312 (Auxiliary Fuse) 616
ZX001:05 321 (Siren/Bell 1 Tamper) 617
ZX001:06 322 (Siren/Bell 2 Tamper) 618
ZX001:07 312 (Siren/Bell 1 Over Current) 619
ZX001:08 312 (Siren/Bell 2 Over Current) 620
ZX001:09 140 (General Alarm) 621