Specifications

PRT-CTRL-SE Protege System Controller Reference Manual | PRT-CTRL-SE 279
Bypass
To access the bypass menu, login using a valid code that is allowed bypass menu access and then select
[MENU, 7]. You can then browse the bypass menu and select the bypass that you want to perform on your
Protege System.
Bypass Menu
The bypass menu consists of 2 entries that can be scrolled to using the [Ð] and [Ï] arrow or selected directly
using the shortcut keys shown in the figure below.
Bypassing Zones
To bypass zones select [MENU, 7, 1] then using the [Ð] and [Ï] arrows to scroll the available zones. A zone
can be bypassed by pressing the [1] key to bypass the zone and then the [2] key to remove the zone bypass. A
zone can also be bypassed in latch mode by pressing the [3] key. If a zone is bypassed normally [1] the zone
bypass will be removed the next time the area disarms, please not all areas that have this zone programmed
must disarm for the bypass to be removed.
y Select the bypass zone menu [MENU, 7, 1]. The display will show the first zone in the system.
Warehouse PIR
is not BYPASSED
y If a normal bypass is required press the [1] key the zone will then toggle state and the display will show the
bypassed message below.
Warehouse PIR
is BYPASSED
y Pressing the [2] key will remove the bypass and pressing the [3] key will bypass the zone in a latched state
requiring that the bypass is removed manually before it will operate again.
i
The Protege System also allows you to search for a zone based on the zone text that is programmed.
To use the search functionality press the [MEMORY] key.
Bypassing Trouble Zones
To bypass trouble zones select [MENU, 7, 2] then using the [Ð] and [Ï] arrows to scroll the available trouble
zones. A trouble zone can be bypassed by pressing the [1] key to bypass the trouble zone and then the [2] key
to remove the trouble zone bypass. A trouble zone can also be bypassed in latch mode by pressing the [3] key.
If a trouble zone is bypassed normally [1] the trouble zone bypass will be removed the next time the area
disarms, please note that all areas that have this trouble zone programmed must disarm for the bypass to be
removed.
y Select the bypass trouble zone menu [MENU, 7, 2]. The display will show the first trouble zone in the
system.