Specifications
PRT-CTRL-SE Protege System Controller Reference Manual | PRT-CTRL-SE 259
Anti-pass back Reset Schedule
If the 'reset anti-passback status on schedule' option has been selected (misc option 5) then all users will have
their anti-passback status reset when the specified schedule becomes valid.
AntiPass Rst Sch
*Schedule 001
Use the [1] and [3] keys to scroll the schedule selection and press [ENTER] to select the schedule displayed.
For more information about the list control data entry refer to the section List Control Data Entry (see page 335).
Register Onboard Reader
The onboard reader functions in the same manner as any other reader expander module and needs to register
at a specific address. This option allows you to define what that address is.
Panel Rdr addr
008
To modify the Onboard reader address (001 to profile maximum), use the keypad as explained in section
Entering Decimal Numbers (see page 333) and press [ENTER]. A value of 255 will disable the Onboard Reader.
Onboard Reader Door Locks
The onboard reader can be configured to use the Panel Bell outputs (CP PGM 1 & 2), the Panel PGM outputs
(CP PGM 3 & 4) or no Panel outputs for it's Door lock PGMs. Note that this setting only applies if, under the
Door set up for the doors accessed by the onboard reader, the lock PGMs are specified as the lock PGMs for
that reader (the default setting).
Panel Rdr o/p
Panel Bells
Use the [1] and [3] keys to scroll the Output setting and press [ENTER] to select the desired output. For more
information about the list control data entry refer to the section List Control Data Entry (see page 335).
Test Report Time
The test report time in conjunction with option 2 sets the time of the day or the period that the test report
trouble zone activates. When option 2 is disabled the time programmed will be used as a period between
reports in hours and minutes.
Test report
time: 02:00
To modify the test report time (00:00 to --:--), use the keypad as explained in the section Entering Time and
Date Values (see page 334) and press [ENTER]. Setting a test report time of --:-- will disable the activation of a
test report.
Automatic Offline User Update Time
The automatic user offline update time in conjunction with option 1 in the miscellaneous options allows the panel
to update the users and other offline parameters on all intelligent modules at a set time of the day.
Offline update
time: 03:00
To modify the offline update time (00:00 to --:--), use the keypad as explained in the section Entering Time and
Date Values (see page 334) and press [ENTER]. Setting an offline update time of --:-- will disable the offline user
update function.