Specifications
PRT-CTRL-SE Protege System Controller Reference Manual | PRT-CTRL-SE 253
Panel Configuration
The panel configuration allows hardware settings to be programmed in to the system controller that affect the
way it operates and functions. To access the panel configuration programming login using a valid installer code
and then select [MENU, 4, 9, 2]. The screen displays the first entry to modify as there is only one panel no
record selection is required. The first item that is programmable is the AC Failure time as shown in the following
example.
AC Failure
time: 030 secs
Every time you press the Enter key, the next screen appears. The different screens are described in the
following sub-sections. Programming the panel settings in the Protege System allow you to configure the
hardware. Some settings that are programmable require that a service that uses the setting is restarted (for
example changing the TCP/IP Address requires that the TCP/IP service is restarted).
AC Failure Time
The AC Failure time allows the installer to program a time that AC mains voltage must have failed before
activating the AC Failure Trouble Zone. Set this to a larger value for locations that experience frequent but short
interruptions in power or that operates on a generator frequently.
AC Failure
time: 030 secs
To modify the AC Failure time (000 to 255 Seconds), use the keypad as explained in section Entering Decimal
Numbers (see page 333) and press [ENTER].
AC Restore Time
The AC Restore time allows the installer to program a time that AC must be present for after a AC Failure before
restoring the AC Failure Trouble Zone. Set this to a larger value for locations that experience frequent but short
interruptions in power or that operates on a generator frequently.
AC Restore
time: 030 secs
To modify the AC Restore time (000 to 255 Seconds), use the keypad as explained in section Entering Decimal
Numbers (see page 333) and press [ENTER].
Battery Test Time
The battery test time allows the installer to program the duration of time in minutes between each battery test
that is performed. A battery test is performed immediately on power up of the panel and then every
programmed period. Each battery test takes 45 seconds and the battery low/failure trouble zone will activate if
the battery fails.
Battery Test
Time: 015 mins
To modify the Battery Test time (000 to 255 Minutes), use the keypad as explained in section Entering Decimal
Numbers (see page 333) and press [ENTER].