Specifications

252 PRT-CTRL-SE Protege System Controller Reference Manual | PRT-CTRL-SE
To modify the C-Bus Group Address enter a value (000 to 255), use the keypad as explained in section Entering
Decimal Numbers (see page 333) and press [ENTER].
Automation Options
Automation options include inverted display and C-Bus automation options. For C-Bus to operate correctly a
Protege PRT-COMM and Clipsal C-Bus PCI interface is required and the C-Bus service must be configured and
started.
AT001 Control
[--------]
To modify options, use the keypad as explained in section Entering Data Options (see page 336).
Option 1 - Automation Display Inverted
y Enabled the Automation display will show the automation status as inverted. Set this option when a PGM or
PGM Group operates inverted to the normal state.
y Disabled the Automation will display in the normally open state.
Option 2 – Enable C-Bus Automation Functions
y Enabled the Automation point will be included in the C-Bus processing and used to control or be controlled
by a C-Bus automation point.
y Disabled the Automation point is not used for C-Bus.
Option 3 - C-Bus Automation Output
y Enabled the Automation point will generate a C-Bus message on the C-Bus system when the status of the
Automation point changes. For example manually controlling the Automation point will send the Application
Id and Group Address to the C-Bus interface.
y Disabled the Automation point is will be updated based on the C-Bus message and group. For example if
this option is disabled and a C-Bus message is received that match's the programmed settings the
automation point will activate the PGM.
Option 4 – Use PGM Status In C-Bus Functions
y Enabled the Automation point will use the programmed PGM directly rather than using the automation point
status or setting. This allows any PGM in the system to be programmed for the automation point without it
actually being controlled by the automation point.
y Disabled the Automation point status will be used for C-Bus operations.
Option 5 – C-Bus Functions Operate On Rising Edge
y Enabled the C-Bus processing will only activate on the rising edge of a change in the Automation Point or
PGM state. For example the Automation point changing from Off to On.
y Disabled the C-Bus processing will ignore any change from Off to On.
Option 6 – C-Bus Functions Operate On Falling Edge
y Enabled the C-Bus processing will only activate on the falling edge of a change in the Automation Point or
PGM. For example the Automation point changing from On to Off.
y Disabled the C-Bus processing will ignore any change from On to Off.
Option 7 and 8 - Reserved
y Reserved do not modify