Specifications

250 PRT-CTRL-SE Protege System Controller Reference Manual | PRT-CTRL-SE
General Programming
The general programming menu contains programmable options for the automation PGM's and the panel
configuration options. The restart menu [MENU, 4, 9, 3] allows the system controller to be restarted.
i
A panel restart is required for the TCP/IP address change to take affect once programmed in the
panel configuration menu. The panel will remain operational on the previously assigned IP address
until it is restarted.
To go to the general menu select [MENU, 4, 9]. You can then select from the menu items presented or scroll
the menu using the [Ï] and [Ð] keys.
Automation
To access the automation programming login using a valid installer code and then select [MENU, 4, 9, 1]. The
screen displays "Automation to modify" as shown in the following example.
Automation to
modify: AT001
Every time you press the Enter key, the next screen appears. The different screens are described in the
following sub-sections. Programming the automation settings in the Protege System allow you to configure the
automation that is shown on the system keypads.
Selecting an Automation Entry to Modify
Each automation entry is assigned a unique automation number from 001 to 250.
Automation to
modify: AT001
Type the appropriate 3-digit automation number or use the [Ð] and [Ï] keys to scroll the available automation
entries. When the desired automation number appears on the screen, press [ENTER] to program the selected
automation entry. The maximum number of automation outputs that can be programmed is limited by your
system's memory and configured profile.