Specifications

248 PRT-CTRL-SE Protege System Controller Reference Manual | PRT-CTRL-SE
Output Register
Select a register to which the output will be written.
FN001 Output
reg: 65535
To modify the Output register (00000 to 65535), use the keypad as explained in section Entering Decimal
Numbers (see page 333) and press [ENTER].
Update Time
Select an Update time. This is the number of seconds between the update of the output register.
FN001 Update
time: 00005 secs
To modify the Update time (00001 to 65535 seconds), use the keypad as explained in section Entering Decimal
Numbers (see page 333) and press [ENTER].
Output Compare
The output compare function will take an input
variable
and scan an input
profile
to select an
output
value which
is then written to an output register. The input register can be any valid register. The input profile is defined as a
range of up to 32 Compare Registers. These registers contain a series of values. The input value is compared
with each compare value, starting from the first one, and if a match is found the corresponding output value is
copied to the output register. A match is found when the Input value lies between the values of one compare
register and the next. The output associated with the compare value that is closest to the input value is then
copied to the output register.
To program the Output Compare function ensure that the function you have selected is halted. Select the
function type selection screen as shown below for the Output Compare function.
FN001 Fnc Type
Output Compare
Use the [1] and [3] keys to scroll the function types until you reach the desired function and press [ENTER] to
select this and proceed to the next programmable option. For more information about the list control data entry
refer to the section List Control Data Entry (see page 335).
Function Mode
The function mode determines how this function operates with the system controller. By default a function is set
to normal operation. Normal operation will mean the function is started if it was running when the system
restarts or is completely powered down (AC Failure and Battery Failure). The Run Once mode of operation will
allow the function to run once and then wait to be stopped and started by the user or operator.
FN001 Fnc Mode
Normal
Use the [1] and [3] keys to scroll the function mode until you reach the normal selection and press [ENTER] to
proceed to the next programmable option for the Output Compare function. For more information about the list
control data entry refer to the section List Control Data Entry (see page 335).
Input Register
This the Register which contains the Input value which gets compared to the profile. It would typically be
assigned to a physical analogue input module.
FN001 Input
reg: 00001