Specifications
246 PRT-CTRL-SE Protege System Controller Reference Manual | PRT-CTRL-SE
Miscellaneous Options
These options are for the function.
FN001 Misc
[1--------]
Halted
Option 1 – Increment on Zone Open
y Enable the counter will increment when the zone opens (alarm).
y Disable.
Option 2 – Increment on Zone Close
y Enable the counter will increment when the zone closes (seal).
y Disable.
Option 3 – Log Counter Events
y Enable the function will log an event for every increment.
y Disable.
Option 4 – Decrement on Zone Open
y Enable the counter will decrement when the zone opens (alarm).
y Disable.
Option 5 – Decrement on Zone Close
y Enable the counter will decrement when the zone closes (seal).
y Disable.
Option 6 – No Overflow on Register
y Enable the counter will not overflow (or underflow) when the register reaches 65535 counting up and 0
when counting down.
y Disabled the register will wrap around to 0 when incremented past 65535 and will wrap around to 65535
when decremented past 0.
Option 7, 8 – Reserved
y Reserved do not modify
Control Zone
The control zone will increment the counter register based on the options selected above.
FN001 Control
Zone CP001:01
Halted
To modify the input Zone, use the settings as explained in section Entering Zones (see page 337).
Counter Register
Enter the Register that will be incremented by the zone. The actual value of the counter is calculated as
(Overflow Register * 65565) + Counter Register.
FN001 Counter
reg: 00100