Specifications
PRT-CTRL-SE Protege System Controller Reference Manual | PRT-CTRL-SE 243
Elevator Action
The action determines what action is performed on the elevator group that is programmed as a result of the
Input PGM. An action MUST be selected for the programmable function to operate correctly.
FN001 Action
None
Use the [1] and [3] keys to scroll the action types until you reach the required action that you want to be
performed and then press [ENTER] to proceed to the next programmable option for the elevator control
function. For more information about the list control data entry refer to the section List Control Data Entry (see
page 335).
y Follow and Test
The floor group status follows the programmed input one state and will retest the input state every 30
second interval and change the floor group state accordingly.
Input One Floor Group
ON UNLOCKED
OFF LOCKED
Test Action - If the floor group state is changed externally or is part of another programmable function the
programmable function will only restore the output state after 30 seconds has elapsed. This time is only
used if the programmable function was NOT responsible for the change in state. If a door has a door unlock
time and the door mode is set to timed this will unlock the door every 30 seconds.
y Not Follow and Test
Performs the same function as above however the output is inverted (NOT). This logic action is a test action,
consult the follow and test action for an explanation of the Test Function.
Input One Output
ON LOCKED
OFF UNLOCKED
y Pulse On
The pulse on action will unlock the floor group only when the input one has transitioned from an off to an on
state. The floor group will not be modified further from this state and will not be modified if it is turned OFF
by another function.
Input One Output
UNLOCKED
y Not Pulse On
The not pulse on action will lock the door only when the input one has transitioned from an off to an on
state. The door will not be modified further from this state and will not be modified if it is turned ON by
another function.
Input One Output
LOCKED
y Pulse Off
The pulse on action will unlock the floor group only when the input one has transitioned from an ON to an
OFF state. The floor group will not be modified further from this state and will not be modified if it is turned
OFF by another function.
Input One Output