Specifications
PRT-CTRL-SE Protege System Controller Reference Manual | PRT-CTRL-SE 241
Option 3 – Alarm on Door Forced
y The Alarm PGM will be activated when the door is forced open.
y The Alarm PGM is not activated.
Option 4 – Pulse Forced Door Alarm
y The Alarm PGM will be activated with a pulse time on and off.
y The Alarm PGM will be turned on normally.
Option 5 – Log Left Open Zone Event
y Enabled the zone events when the door is left open.
y Disables the zone events from being generated.
Option 6 – Log Forced Zone Event
y Enabled the zone events when the door is forced open.
y Disables the zone events from being generated.
Option 7 and 8 - Reserved
y Reserved do not modify
Zone Follows PGM Function
To program the zone follows pgm function ensure that the function you have selected is halted. Select the
function type selection screen as shown below for Zone Control.
FN001 Func Type
Zone Control
Use the [1] and [3] keys to scroll the function types until you reach the door control selection and press [ENTER]
to select the function type displayed and proceed to the next programmable option for the door control function.
For more information about the list control data entry refer to the section List Control Data Entry (see page 335).
Function Mode
The function mode determines how this function operates with the system controller. By default a function is set
to normal operation. Normal operation will mean the function is started if it was running when the system
restarts or is completely powered down (AC Failure and Battery Failure). The Run Once mode of operation will
allow the function to run once and then wait to be stopped and started by the user or operator.
FN001 Func Mode
Normal
Use the [1] and [3] keys to scroll the function mode until you reach the normal selection and press [ENTER] to
proceed to the next programmable option for the door control function. For more information about the list
control data entry refer to the section List Control Data Entry (see page 335).
Control Zone
The control zone's state will be set to be opened or closed according to the start of the Control PGM. If the
PGM is OFF the zone will be closed. If the PGM is ON, TIMED ON or PULSED ON the zone will be open.
The zone must be placed in an armed area to use it for control or reporting.
FN001 Control
Zone CP001:01
Halted
To modify the input Zone, use the settings as explained in section Entering Zones (see page 337).