Specifications

PRT-CTRL-SE Protege System Controller Reference Manual | PRT-CTRL-SE 239
Rex Zone Input
The Request to Exit (REX) Input is connected to the Virtual Door's REX Zone. When this zone is closed the
Lock PGM is activated and the door can be opened for the Max Open time when no alarms being generated.
This zone should be configured as a digital zone, therefore disable the "EOL Resistor on zone input" option. If
a Normally Closed REX button is used the zone should inverted option should be set for the zone to ensure
pushing the button will generate the REX event.
This zone must also be placed in an armed area for the Virtual Door to operate.
FN001 REX
Zone CP001:01
Halted
To modify the input Zone, use the settings as explained in section Entering Zones (see page 337).
Door State Zone Input
The Door Position input is connected to the Door State Zone. This should be configured so that when the
door opens the zone opens. It may be necessary to invert the zone input to ensure this operation.
This zone should be configured as a digital zone, therefore disable the "EOL Resistor on zone input" option.
This zone must also be placed in an armed area for the Virtual Door to operate.
FN001 Door State
Zone CP001:01
Halted
To modify the input Zone, use the settings as explained in section Entering Zones (see page 337).
Virtual Door Left Open Zone
When programmed this zone is controlled by the Virtual Door Function such that when the door is left open
longer than the Max Open time and a Door Left Open event is generated this zone will be opened. When the
door closes, the zone will also close. Place this zone in a reportable area to enabled reportable events from
the virtual door.
FN001 Left Open
Zone CP001:01
Halted
To modify the input Zone, use the settings as explained in section Entering Zones (see page 337).
Virtual Door Forced Open Zone
When programmed this zone is controlled by the Virtual Door Function such that when the door is forced open
and a Door Forced Open event is generated this zone will be opened. When the door closes, the zone will also
close. Place this zone in a reportable area to enabled reportable events from the virtual door.
FN001 Forced
Zone CP001:01
Halted
To modify the input Zone, use the settings as explained in section Entering Zones (see page 337).