Door Mode Description
Menu Latched The door will be latched in the unlocked state and will remain unlocked until controlled
from:
A LCD Keypad
Protege System Management Suite
Scheduled Action
Area Status
A Programmable function.
Fire Control The door will be latched in the fire control unlock state and will remain unlocked until
controlled from:
A LCD Keypad
Protege System Management Suite
A Programmable function that is programmed to deactivate the fire alarm control.
Lockdown Door Lockdown will be started for the door or door group and will remain Protege an
LCD Keypad or when the PGM input goes off if the function is operating in a Test and
Follow mode.
Lockdown (Entry
Allowed)
Door Lockdown with Entry Allowed will be started for the door or door group and will
remain locked down until it is cancelled from the Protege System Management Suite,
an LCD Keypad or when the PGM input goes off if the function is operating in a Test
and Follow mode.
Lockdown (Exit
Allowed)
Door Lockdown with Exit Allowed will be started for the door or door group and will
remain locked down until it is cancelled from the Protege System Management Suite,
an LCD Keypad or when the PGM input goes off if the function is operating in a Test
and Follow mode.
Lockdown (Entry and
Exit Allowed)
Door Lockdown with Entry and Exit Allowed will be started for the door or door group
and will remain locked down until it is cancelled from the Protege System Management
Suite, an LCD Keypad or when the PGM input goes off if the function is operating in a
Test and Follow mode.
Virtual Door Function
To program the virtual door function ensure that the function you have selected is halted. Select the function
type selection screen as shown below for the Virtual Door.
FN001 Func Type
Virtual Door
Use the [1] and [3] keys to scroll the function types until you reach the door control selection and press [ENTER]
to select the function type displayed and proceed to the next programmable option for the door control function.
For more information about the list control data entry refer to the section List Control Data Entry (see page 335).
Function Mode
The function mode determines how this function operates with the system controller. By default a function is set
to normal operation. Normal operation will mean the function is started if it was running when the system
restarts or is completely powered down (AC Failure and Battery Failure). The Run Once mode of operation will
allow the function to run once and then wait to be stopped and started by the user or operator.
FN001 Func Mode
Normal
Use the [1] and [3] keys to scroll the function mode until you reach the normal selection and press [ENTER] to
proceed to the next programmable option for the door control function. For more information about the list
control data entry refer to the section List Control Data Entry (see page 335).