Input One PGM
Input one selects the input source to the door control process that is being configured. All door control functions
use at least one input source. Input one must be programmed with a valid input source, if an input source is
selected that is not valid when the function is started an error will be generated and the function suspended. An
input source can be a PGM (Programmable Output).
FN001 Input one
pgm: --000:00
To modify the input PGM, use the settings as explained in section Entering PGM and PGM Groups (see page
336).
Control Door
The control door selects the door to control as a result of the action being performed by the programmable
function. To control a door group leave the control door option set to none and proceed to the Control Door
Group entry screen. Selecting both a door and a door group will result in only the door being controlled and the
door group being ignored.
FN001 Door
None
Use the [1] and [3] keys to scroll the action types until you reach the door that you want to control and then
press [ENTER] to proceed to the next programmable option for the door control function. For more
information about the list control data entry refer to the section List Control Data Entry (see page 335).
Control Door Group
The control door group selects the area group to control as a result of the action being performed by the
programmable function. To control a door leave the control door group set at none and program a door in the
control door section. Programming a door and a door group will result in the door group not being used.
FN001 Door Grp
None
Use the [1] and [3] keys to scroll the door groups until you reach the required group and then press [ENTER] to
proceed to the next programmable option for the door control function. For more information about the list
control data entry refer to the section List Control Data Entry (see page 335).
Door Control Mode
The control mode selects how the door will be controlled in the control door or control door group setting. This
allows a door to be unlocked for the door unlock time, unlock latched or unlocked in the fire alarm mode.
FN001 Door Mode
Menu Timed
Use the [1] and [3] keys to scroll the door control mode until you reach the setting that you want to use and then
press [ENTER] to proceed to the next programmable option for the door control function. For more
information about the list control data entry refer to the section List Control Data Entry (see page 335).
Door Mode Description
Menu Timed The Door will be unlocked for the door unlock time that is programmed for the door.
Use this mode when you want to unlock the door for unlock time. The door will lock
after the unlock time has expired.