Specifications

PRT-CTRL-SE Protege System Controller Reference Manual | PRT-CTRL-SE 233
Function Mode
The function mode determines how this function operates with the system controller. By default a function is set
to normal operation. Normal operation will mean the function is started if it was running when the system
restarts or is completely powered down (AC Failure and Battery Failure). The Run Once mode of operation will
allow the function to run once and then wait to be stopped and started by the user or operator.
i
Setting the run once option for the ripple PGM function will result in NO operation being performed
and the function stopping a short time after it is started.
FN001 Func Mode
Normal
Use the [1] and [3] keys to scroll the function mode until you reach the normal selection and press [ENTER] to
move to the next programmable option for the ripple PGM function. For more information about the list control
data entry refer to the section List Control Data Entry (see page 335).
Enabled Control PGM
The Enabled Control PGM is used to operate the ripple PGM function in the STEP UP mode when it is activated
and it will run in the STEP DOWN mode when the Enable PGM is deactivated. If no enabled PGM is set the
function will never run the ripple stages.
FN001 Enabled
pgm: --000:00
To modify the enabled PGM, use the settings as explained in section Entering PGM and PGM Groups (see page
336). To select a data register press the stay key, the following screen will be shown and a memory register
location can be selected. To view the memory register locations refer to appendix memory registers.
Ripple On Time
The ripple on time determines the time that each PGM output will be delayed before being activated when the
ripple control function is stepping the PGM outputs up.
FN001 Ripple on
time: 00000 secs
To modify the ripple on time (00000 to 65535 seconds), use the keypad as explained in section Entering
Decimal Numbers (see page 333) and press [ENTER].
Ripple Off Time
The ripple off time determines the time that each PGM output will be delayed before being deactivated when the
ripple control function is stepping the PGM outputs down.
FN001 Ripple off
time: 00000 secs
To modify the ripple off time (00000 to 65535 seconds), use the keypad as explained in section Entering
Decimal Numbers (see page 333) and press [ENTER].