Specifications
PRT-CTRL-SE Protege System Controller Reference Manual | PRT-CTRL-SE 229
Register Offset Register Function
7
Manual Cooling Reverse
The manual reverse (cooling) override PGM is active and the floor tempering is operating
in Manual Cooling mode.
8
RTHP Shutting Down
The floor tempering is completing an orderly shutdown of the currently activated outputs
and the fan control signal.
9
Fault Condition
A fault condition has activated that has caused the floor tempering to shut down. This
condition is typical of a smoke damper closing or other mechanical input that will result in
the floor tempering shutting down.
10
Fire Condition
A fire alarm condition has been activated that has caused the floor tempering to shut
down.
11
Mode Delay
The mode has changed during a controlled operation either from Manual to Auto or Auto
to Manual and the function has entered a delay period.
Floor Temperature Register
The floor temperature register is the register that is updated by an analogue module input channel connected to
a temperature sensor located at the floor level which is operated by the floor tempering system. The floor
temperature is typically received from a sensor located within the floor area being controlled.
FN001 Floor temp
reg: 00000
To modify the floor temperature register (00000 to 65535, use the keypad as explained in section Entering
Decimal Numbers (see page 333) and press [ENTER].
i
If you are unsure how the Floor Tempering function operates and what action is going to be started as
a result in the change in the input registers you can specify the register to be a normal register outside
the analogue module range. This will allow an installer to modify the values with the Protege System
Management Suite and visually see the mode change in the Floor Tempering without the need to
physically connect the Floor Tempering to mechanical devices.
Duct Temperature Register
The duct air temperature register is the register that is updated by an analogue module input channel connected
to a temperature sensor. The duct air temperature is typically from a sensor located within the duct downstream
(when operating in forward mode) of the duct fan.
FN001 Duct temp
reg: 00000
To modify the duct temperature register (00000 to 65535, use the keypad as explained in section Entering
Decimal Numbers (see page 333) and press [ENTER].