Fault PGM
The fault control PGM is set when a fault condition has occurred and the Floor Temping is to shutdown. This
allows the Floor Temping to shutdown in the shortest possible time without causing any damage to the system.
In the case of a fire shutdown the system must have a fire PGM programmed.
FN001 Fault
pgm: --000:00
To modify the fault PGM, use the settings as explained in section Entering PGM and PGM Groups (see page
336).
Fire PGM
The fire control PGM is monitored NOT controlled by the function and when the fire PGM has been activated,
typically by an external fire alarm input, the floor tempering will gracefully shut down the system and halt
operation until the fire alarm has been cleared. This PGM could be the PGM used to deactivate smoke dampers
and other related equipment in the HVAC control system.
FN001 Fire
pgm: --000:00
To modify the fire PGM, use the settings as explained in section Entering PGM and PGM Groups (see page
336). Do not set a PGM group for the fire or other monitored PGM's as this will have no action in the control
system and will be the same as not setting a PGM value.
Fan Control PGM
The fan PGM is activated when the floor tempering starts to operate and is started 30 seconds prior to any
heating or cooling. The direction of the fan (forward and reverse) is determined by the forward and reverse PGM
outputs. If a fan on signal is not required use the forward and reverse PGM outputs to drive the appropriate
contactors.
FN001 Fan
pgm: --000:00
To modify the fan PGM, use the settings as explained in section Entering PGM and PGM Groups (see page
336).
Forward PGM
The forward PGM is used to drive the fan in the forward direction this will circulate air from the intake through
the heating element and towards the floor. In the forward mode the temperature at the floor is below the set
point.
FN001 Forward
pgm: --000:00
To modify the forward PGM, use the settings as explained in section Entering PGM and PGM Groups (see page
336).
Reverse PGM
The reverse PGM is used to drive the fan in the reverse direction this will circulate air from the floor and return
this to the intake. In the reverse mode the temperature at the floor is above the set point.
FN001 Reverse
pgm: --000:00
To modify the reverse PGM, use the settings as explained in section Entering PGM and PGM Groups (see page
336).