The Base data register is used as the first register in the list of registers used to configure, program and control
the RTHP. The only registers that are not included in the base registers are ones that must link to an analog
input or analog output for external sensors (Temp, Humidity or Dampers). A base data register setting MUST be
set.
FN001 Space rh
reg: 00000
To modify the base data register (00000 to 65535, use the keypad as explained in section Entering Decimal
Numbers (see page 333) and press [ENTER].
Floor Tempering Control Function
The Floor Tempering programmable function allows the direct control of a single stage floor tempering system
that controls a duct mounted heater and/or cooling compressor. The support for one heating and one cooling
state is provided as well as a forward and reverse operation.
FN001 Func Type
Floor Temping
Use the [1] and [3] keys to scroll the function types until you reach the Floor Temping selection and press
[ENTER] to select the function type displayed and proceed to the next programmable option for the Floor
Temping control function. For more information about the list control data entry refer to the section List Control
Data Entry (see page 335).
Function Mode
The function mode determines how this function operates with the system controller. By default a function is set
to normal operation. Normal operation will mean the function is started if it was running when the system
restarts or is completely powered down (AC Failure and Battery Failure). The Run Once mode of operation will
allow the function to run once and then wait to be stopped and started by the user or operator. Setting the run
once option for the RTHP will result in NO operation being performed and the function stopping a short time
after it is started.
FN001 Func Mode
Normal
Use the [1] and [3] keys to scroll the function mode until you reach the normal selection and press [ENTER] to
proceed to the next programmable option for the floor temping function. For more information about the list
control data entry refer to the section List Control Data Entry (see page 335).
Enabled Control PGM
Enabled Control PGM is set when the Floor Temping is to run and will operate only when the enabled PGM is
on. If no enabled PGM is set the Floor Temping will run continuously. Programming a PGM that is activated by a
schedule allows the floor temping to operate only during the times that the space is occupied.
FN001 Enabled
pgm: --000:00
To modify the enable PGM, use the settings as explained in section Entering PGM and PGM Groups (see page
336).