Specifications

PRT-CTRL-SE Protege System Controller Reference Manual | PRT-CTRL-SE 215
Area Action
The action determines what action is performed on the area or area group that is programmed as a result of the
Input PGM. For key switch arming or simple arming of an area from a zone input use the area control options in
the zone type configuration. Refer to the Zone Type Programming (see page 99).
FN001 Action
None
Use the [1] and [3] keys to scroll the action types until you reach the required action that you want to be
performed and then press [ENTER] to proceed to the next programmable option for the area control function.
For more information about the list control data entry refer to the section List Control Data Entry (see page 335).
y Follow and Test
The area status follows the programmed input one state and will retest the input state continually.
Input One Area Control
ON ARM
OFF DISARM
Test Action - If the output state is changed externally or is part of another programmable function the
programmable function will only restore the output state after 30 seconds has elapsed. This time is only
used if the programmable function was NOT responsible for the change in state.
y Not Follow and Test
Performs the same function as above however the area control function is inverted (NOT). This logic action
is a test action, consult the follow and test action for an explanation of the Test Function.
Input One Area Control
ON DISARM
OFF ARM
y Pulse On
The pulse on action will arm the area only when the input one has transitioned from an off to an on state.
The area will not be modified further from this state and will not be modified if it is turned OFF by another
function.
Input One Area Control
ARM
y Not Pulse On
The not pulse on action will disarm the area only when the input one has transitioned from an off to an on
state. The area will not be modified further from this state and will not be modified if it is turned ON by
another function.
Input One Area Control
DISARM
y Pulse Off
The pulse on action will arm the area only when the input one has transitioned from an ON to an OFF state.
The area will not be modified further from this state and will not be modified if it is turned OFF by another
function.
Input One Area Control
ARM